Maintain precise blended water quality with the Softcontrol-V/UE Blend water hardness analyser. Specifically designed for applications requiring controlled water hardness, the system continuously measures calcium and magnesium levels using advanced potentiometric sensing technology.
Programmable alarm limits allow operators to define acceptable hardness levels, while configurable alarm delays help eliminate unnecessary alerts. Should the preset limit be exceeded, a relay contact activates to notify operators immediately.
With integrated USB data logging and reagent-free operation, Softcontrol-V/UE delivers reliable water hardness monitoring while reducing maintenance costs and environmental impact.
| Wall Mounted | 400 x 250 x 160 mm (W x H x D) |
|---|---|
| Weight | Approx 8 kg |
| Surrounding Temperature | 5 °C … 50 °C |
| Relative Humidity | 20 % … 80 % |
| Power Supply | 100 … 240 Volt / 50 … 60 Hz |
| Power Consumption | 15 V DC, about 20 Watt |
| Raw and Blended Water Connection | Branch pipe with connection for PA-tube o.d. 4 mm, i.d. 2 mm, up streamed dirt filter ≤ 0,1 mm recommended |
| Raw and Blended Water Pressure | Minimum 1 bar up to maximum 10 bars |
| Drain | Minimum ø 15 mm, pressure free |
| Quality of Raw and Soft Water | Natural water, free of grease, oil and brine germ content < 5000 CFU/ml |
| Hardness Range Raw Water | 0.72 ppm 32.4 ppm |
| Possibility of Calibration Input Actual Value of Blended Water Hardness | 0.2 ppm 10,8 ppm |
| Setting of Threshold Value | 0.2 ppm 10,8 ppm |
| Sensor Control | Automatic |
| External Signaling | Potential-free contacts (sensor alarm, threshold value alarm) 4 … 20 mA current loop, paramterisable |
| Operation Time of Sensor | Approx. 6 to 9 months |