Protect your water treatment system with the Softcontrol Smart hardness monitoring device. Designed for continuous operation, it accurately detects hard water intrusion and activates an alarm whenever the fixed threshold value of 10% of inlet water hardness is exceeded.
The compact unit delivers dependable performance while reducing the need for ongoing monitoring and maintenance, making it ideal for commercial and industrial water softening systems.
Softcontrol Smart is particularly well suited for installations with reverse osmosis systems where reliable soft water quality is essential.
| Dimensions of case | 120 x 80 x 55 mm (B x H x D) |
| Mounting Area Weight | 220 x 300 x 65 mm (B x H x D) (wall mounted) |
| Weight | appr. 500 g |
| Surrounding Temperature | 5°C to 50°C |
| Relative Humidity | 20% to 80% |
| Power Supply | Wall power supply 100 … 240 V / 50 … 60 Hz |
| Power Consumption | 15 V DC, approx. 4 Watt |
| Raw and Soft Water Connections | Branch pipe with connection for PA-tube o.d. 4 mm, i.d. 2 mm, up streamed dirt filter ≤ 0,1 mm recommended |
| Raw and Soft Water Pressure | Minimum 1 bar up to maximum 10 bars |
| Drain | Minimum ø 8 mm, pressure free |
| Quality of Raw and Soft Water | Natural water, free of grease, oil and brine germ content < 5000 CFU/ml |
| Hardness Range Raw Water | 0.18 ppm up to 10.8 ppm, natural water |
| Evaluation of Water Hardness in Soft Water | From 0.018 ppm |
| Operation Time of Sensor | Approx. 6 to 9 months |